The Kidde Sentinel System provides a fully integrated fire detection and suppression solution to meet the most challenging fire hazards for vehicles in forestry applications, agribusiness and mining operations.
Thursday, September 29, 2011
Monday, September 26, 2011
ARIES® NETLink SYSTEM CONTROL UNITS
The ARIES NETLink is a fully featured and cost competitive multi-loop, intelligent, addressable and networkable Fire Suppression Control Panel designed for commercial, industrial and high tech facilities.
The ARIES NETLink is the technologically most advanced multi-loop control unit available to the industry today. Dependability and maximum protection against inadvertent release are hallmarks of Kidde Fire Systems panels. We build in safeguards so that no single component failure or combination of abnormal operating conditions, including main-microprocessor failure is allowed to result in accidental release activation.
At its core, the ARIES NETLink is a suppression panel; approved for use with Clean Agents, CO2, Wet and Dry Chemical Systems as well as water based systems such as Water Mist, Water Deluge, Pre-action and Foam. It combines the high quality, system reliability, and flexibility required by modern commercial, high-tech and industrial applications in an aesthetically pleasing and physically robust package.
Features
- Reliable and dependable suppression control that features Triple-R redundancy
- Expandable from 3 to 8 SLCs (2,040 addresses)
- Networkable up to 64 nodes with 130,560 addresses across network
- Event-Output-Control programming
- High level serviceability and diagnostics
- Backwards compatible with installed base of SmartOne devices, network and suppression releases (control heads, solenoids, initiators)
- Network supports both copper wire and fiber optic cable
Technical Specifications
- 2 SLC with 255 SmartOne® Addresses each
- 4 x 40 Display-Keypad
- 2 Notification and 2 Release/ Notification Circuits
- 3 Programmable and 1 Trouble Form-C Relays
- USB Ports for PC and Printer
- 4 Installer Programmable Soft-Switches
- 10,000 Event Log Capacity
Listing & Approvals
- FM Approved
- UL Listed
- cUL Listed
- CSFM
- NYC Fire Department Approved
Sunday, September 25, 2011
Fenwal Spherical FM-200® System
Features:
Environmentally friendly, sustainable technology
Clean and Non-Toxic, safe for use in occupied spaces
Design for maximum protection with minimum hardware, less space and lower cost
Wide range of product offerings for best economical fit to application
Compatible with all of Fenwal’s various detection and control options
Technical Specifications:
Fast acting 10 second discharge
Designed per NFPA 2001, total flooding systems
Offered in fill ranges from 20 to 196 lb. of agent
Listed and Approved for applications in the temperature range of 32°F to 130°F
Listings/Approvals:
UL Listed
UL Canada (ULC)
Factory Mutual Approved
MEA Listed
If you have any questions or concerns. Please feel free to contact us any time through this web site or through this E-mail: Sales@TTLCompany.com | Web: http://TTLCompany.com
Fenwal Phoenix FM-200® System
The Fenwal Phoenix System is a high performance suppression system developed to provide economic protection for large fire protection projects and specialized applications. Although the Phoenix System is considered the best alternative as a drop-in replacement of your Halon system, It is widely used in protection of large telecommunications facilities, museums, and data storage systems for banks and financial institutions.
Features:
Provide active fire protection when coupled with Fenwal’s various 24 hr detection and control systems.
Increased flow performance allows for remote location of cylinders.
Increased performance deems it a virtual “Drop-in” replacement for installed Halon 1301 systems.
Listed and approved with 3-way directional valves for economic protection of multiple enclosures.
Technical Specifications:
Utilizes a patented “Fan Type” nozzle for immediate vaporization of the agent as it discharges.
Uses separate nitrogen storage as a propellant to obtain higher mass flow rates.
Can be design to achieve 140% agent in pipe and still achieve a
10-second discharge at the nozzle.
Listings/Approvals:
UL Listed
UL Canada (ULC)
Factory Mutual approved
MEA
If you have any questions or concerns. Please feel free to contact us any time through this web site or through this E-mail: Sales@TTLCompany.com | Web: http://TTLCompany.com
FENWAL ANALASER® II HSSD SYSTEM
The AnaLASER II HSSD is an air sampling system that is 2000 times more sensitive than conventional smoke detectors. The higher sensitivity of the detector allow it to detect low energy fires even in high airflow environments which tend to dilute smoke concentrations.
Features:
Laser particle-counting technology
Uses particle size discrimination technology—no filter required!
Full configuration using LaserNET™ software
History buffer stores up to 28 days of smoke history
Technical Specifications:
Up to 20,000 sq. ft. of coverage
Programmable sensitivity range:
- Ultra Detector:0.00015%/ft. to 0.03%/ft. obs.
- Standard Detector: 0.00075%/ft. to 0.3%/ft. obs.
Use with IIM to network up to 127 detectors
If you have any questions or concerns. Please feel free to contact us any time through this web site or through this E-mail: Sales@TTLCompany.com | Web: http://TTLCompany.com
Fenwal Bottom-Discharge Systems
The Fenwal Bottom-Discharge System is the preferred fire suppression system for protection of mission critical facilities that can’t afford fire-related business interruption. It utilizes the world’s most trusted, waterless clean agent, FM-200.Installation of these systems are found all over the world protecting Data Centers, IT facilities, Telecomm, Switchgear rooms and more.
Features:
Environmentally friendly, sustainable technology
Clean and Non-Toxic, safe for use in occupied spaces
Design for maximum protection with minimum hardware, less space and lower cost
Wide range of product offerings for best economical fit to application
Compatible with all of Fenwal’s various detection and control options
Technical Specifications:
Fast acting 10 second discharge
Designed per NFPA 2001, total flooding systems
Offered in fill ranges from 150 lb to 850 lb. of agent
Listed and Approved for applications in the temperature range of 32°F to 130°F
Listings/Approvals:
UL Listed
UL Canada (ULC)
Factory Mutual Approved
MEA Listed
If you have any questions or concerns. Please feel free to contact us any time through this web site or through this E-mail: Sales@TTLCompany.com | Web: http://TTLCompany.com.0
Friday, September 23, 2011
Kidde WHDR™ Kitchen Wet Chemical System
Fenwal 9300 Series FM-200® System
Fenwal 9300 Series FM-200® System
The Fenwal 9300 Series is the preferred fire suppression system for protection of mission critical facilities that can't afford fire-related business interruption. It utilizes the world's most trusted agent, FM-200. The Fenwal 9300 System has proven experience—it can be found installed in data centers, IT facilities, telecommunication centers, switch gear rooms and more around the world…
Features:
Environmentally friendly, sustainable technology
Clean and non-toxic—safe for use in occupied spaces
Designed with maximum protection with minimal hardware, less space and lower cost
Wide range of product offerings for best economical fit to application
Compatible with all of Fenwal's various detection and control options
Technical Specifications:
Fast acting 10 second discharge
Designed per NFPA 2001, total flooding systems
Offered in fill ranges from 5 lb. to 900 lb. systems
Listed and Approved for hazard temperatures from 32°F to 130°F
Listings/Approvals:
UL Listed
ULC Listed (Canada)
Factory Mutual Approved
MEA Listed
If you have any questions or concerns. Please feel free to contact us any time through this web site or through this E-mail: Sales@TTLCompany.com | Web: http://TTLCompany.com.
High-Sensitivity Smoke Detection (HSSD)
| ||||||||||||||||||||
On-Line Documentation |
Kidde FE-13 Suppression System
Kidde FE-13 Suppression System
The Kidde FE-13 Suppression System is designed for protection of applications in low temperature environments and high-ceiling structures or where a high concentration of fire suppression agent is required to inert the protected application against fire. Uses clean, fast, people-safe FE-13 gaseous agent that works by absorbing heat from the fire. System includes detectors, a control unit, agent storage cylinders, piping and discharge nozzles.
Features:
• Listed and approved for use by the U.S. EPA
• Ideal for inerting environments
• Tested and approved all of Kidde's various detection and control options
• Flexible design to fit your application
Technical Specification:
• Provides it own source of propellant with a high vapor pressure
• Extinguishes fire both physically and chemically
• Very low boiling point to allow a discharge to gas as low temperatures (140° F)
• Typical use concentration at 18% - NAOEL at 30% - High Safety Margin
• Approved for hazards with 25 foot ceiling heights
If you have any questions or concerns. Please feel free to contact us any time through this web site or through this E-mail: Sales@TTLCompany.com | Web: http://TTLCompany.com.
Kidde Novec™ 1230 Fire Protection Fluid System
Kidde Novec™ 1230 Fire Protection Fluid System
Kidde Engineered Fire Suppression System Designed for Use with 3M™ Novec™ 1230 Fire Protection Fluid is engineered to provide clean, fast, people-safe protection for applications requiring a “green” solution to fire suppression. The system includes detectors, a control unit, agent storage cylinders, piping and discharge nozzles. The system is computer calculated to provide system discharge within 10 seconds.
Technical Specifications:
Novec™ 1230 Fluid presents distinct environmental benefits, including a zero Ozone Deletion Factor (ODP) and the lowest Global Warming Potential (GWP) of an chemical based clean agent, key to satisfying demands of environmentally sensitive markets and end-users.
The Engineered System offering—
allows design flexibility using our
Novec™ 1230 Fire Protection Fluid
system design software.
Provides a high safety margin with a
4.2% use concentration and a 10%
NOAEL and > 10% LOAEL level.
Listed for hazard temperatures
between 0°F and 132°F.
Benefits:
• Provides a high safety margin with a 4.2% use concentration and a 10% NOAEL level.
• Listed for protection against Class A, Class B and Class C fires.
• Is a fluid a atmospheric pressure and can be gravity fed for easy re-charge.
• Extinguishes fire through heat absorption and not oxygen reduction.
Listings/Approvals:
UL
ULC
Factory Mutual Approved
MEA
Kidde ECS Series FM-200® Fire Suppression System
Environmentally-friendly. The preferred fire suppression system for vital facilities that can't afford fire-related business interruption of process controls, automated industrial operations, robotics, etc. Active on fire, but inert on people; non-toxic when used per NFPA Standard 2001. Safe, no-residue protection for Class A, B and C fires. Every Kidde system checked for design accuracy. Designed for maximum protection with minimum hardware; less space, lower cost. UL Listed and Factory Mutual approved.
Features:
• Reduces risk of downtime and helps maintain business continuity in the event of a fire.
• Clean leaving no residue. Safe for discharge into occupied spaces.
• Design concentrations for 95% of its applications fall well below NOAEL levels.
• Cost effective engineered system, providing maximum protection.
• Proven Kidde Reliability - tested and approved all of Kidde's various detection and control options.
• Sustainable technology providing an environmentally-friendly solution.
Technical Specifications:
• FM-200 agent actively attacks the fire to extinguish flames rapidly
• Engineered system providing a fast acting 10 second discharge
• Offers full-developed, flexible design limits to fit any application environment
• Design concentrations range from 6.25% to 7.0% for Class A and Class C hazards
• Easy to design using Engineered Series software
If you have any questions or concerns. Please feel free to contact us any time through this web site or through this E-mail: Sales@TTLCompany.com | Web: http://TTLCompany.com
Kidde ADS Series FM-200 Fire Suppression System
Kidde Argonite® Fire Suppression System
Thursday, September 22, 2011
Kidde CO2 (Carbon Dioxide) Fire Suppression Systems
The Kidde Carbon Dioxide Fire Suppression System is an engineered system available in three application configurations: total flooding (for unoccupied areas), local application or hand-hose line. System includes detectors, a control unit, agent storage cylinders, piping and discharge nozzles. Gaseous carbon dioxide rapidly suppresses fire by a combination of cooling and oxygen displacement. Discharge duration and agent flow rates are customized for the individual application.
Recommended for protection of unoccupied facilities. Economical, computer-designed and engineered; using total flooding, hand hose line and/or local application. The most technologically advanced CO2 fire suppression systems available. Colorless, odorless and electrically nonconductive. Rapid cleanup equals minimal downtime.
We install Kidde Carbon Dioxide (C02) fire suppression systems. C02 gas has a high ratio of expansion which facilitates rapid discharge and allows for three dimensional penetration of the entire hazard area quickly. Carbon Dioxide extinguishes a fire by reducing the oxygen content of the protected area below the point where it can support combustion. Carbon Dioxide Fire extinguishing systems typically store the agent in one of two different ways, high pressure cylinders, or low pressure CO2 tanks.
Advantages of Carbon Dioxide
When designed, engineered, and installed properly, Carbon Dioxide fire suppression systems will not damage sensitive electronic equipment. Carbon Dioxide has no residual clean-up associated with its use as a fire suppression agent. Carbon Dioxide fire extinguishing systems can be used to protect a wide variety of hazards, from delicate electronic equipment to high-voltage electrical equipment, all without causing damage to the equipment being protected.
Technical Specifications:
• Reduces the oxygen content of the atmosphere to a point where combustion becomes impossible.
• Hardware to accommodate any application and system type
• Offered in 25 lb to 100 lb Cylinders
• Hose reel line systems
• Directional valve system options
• Lockout valves and lockout circuits
Features:
• Proven quality and reliability with the Kidde brand
• Tested and approved all of Kidde's various detection and control options
• Inexpensive and plentiful to re-fill
• Wide ranges of proven safe, hazard protection
CO2 Is Versatile. Used on a wide variety of hazards throughout the world:
• Flammable liquid storage
• Printing presses
• Mixing Operations
• Spray Booths
• Industrial Ovens
• Dust Collectors
• Paint Lockers
• Marine Applications
Elements of a CO2 Fire Suppression System
A Carbon Dioxide Fire Suppression system consists of one or more banks of cylinder storage containers to supply the CO2 extinguishing agent. Flexible discharge bends, or hoses, connect the cylinders into a piping manifold. The manifold in turn distributes the agent into the piping network. Nozzles regulate the flow of CO2 into the protected area.
Before Carbon Dioxide is released into the protected facility, fire must be detected by a detection and control system. We use the Pegasys addressable control panel for Kidde systems and the Auto pulse control panel for CO2 systems.
Experience
We have extensive experience in the installation and design of CO2 fire suppression systems; in fact we have installed and maintained CO2 systems since our inception in 1999.
We have worked with major corporations to design CO2 systems nationwide for a variety of applications. Call today and speak with one of our knowledgeable professionals.
Listings/Approvals: UL Listed, FM, MEA, USCG