ARIES NETLink™ Fire Alarm-Suppression Control Unit

ARIES NETLink Fire Alarm-Suppression Control Unit

The ARIES NETLinkTM is a fully featured and cost competitive Multi-Loop, Intelligent Addressable, Networkable, Expandable, Fire Alarm- Suppression Control Panel designed for commercial, industrial, high tech and heritage facilities that include fire detection, alarm notification and suppression as part of their overall risk management strategy. At its core, the ARIES NETLinkTM is a suppression panel; approved for Clean Agents, CO2, Wet and Dry Chemical Systems as well as water based systems such as Water Mist, Water Deluge, Pre-action and Foam.

Base Unit Out-of-the-box Technical Specifications:
  • 2 SLC with 255 SmartOne Addresses each
  • 4 x 40 Display-Keypad
  • 2 Notification and 2 Release/ Notification Circuits
  • 3 Programmable and 1 Trouble Form-C Relays
  • 2 Auxiliary Power Outputs rated 1 Amp each @ 24 VDC
  • USB Ports for PC and Printer
  • RS-232 Ports for Graphics
  • 4 Installer Programmable Soft-Switches
  • 10,000 Event Log Capacity
  • RS-485 Annunciator Network
  • 120/240 V 50/60 Hz AC Input
  • 5.4 A Power Supply Unit
  • NEMA 1 Enclosure - Fits between 16" Studs
Features
  • SLC loops have no restrictions of SmartOne device type
  • Backwards compatible with installed base of SmartOne devices, network and suppression releases (control heads, solenoids, initiators)
  • Network supports both copper wire and fiber optic cable
  • Maintains use of Event Output Control (EOC) programming – enables complex releasing sequences
  • Advanced troubleshooting and diagnostic tools - ground fault detection by circuit
  • Provides migration strategy for installed base - retrofit kit
  • Power supply behind hinged main board reduces control unit footprint and enables easy access
  • Terminal blocks plug-in / plug-out for easy service
  • Multiple knockouts enable efficient wire routing
  • 2-Tier and 3-Tier enclosure options
  • On-board SLC switches enable quick disconnects
  • Release circuits feature built-in NFPA-72 compliant maintenance switches
  • Class A and B wiring on SLC, NAC and ARC – requires no additional hardware
  • All the above with a 36-month warrantyunsurpassed in the industry
  • Integrates seamlessly with HSSD, ASD and LHD detection devices on SLC loop - ability unsurpassed in the industry; lowers overall cost of system